HL B-Series Air Cooled Chillers
HL B-10
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-10
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 10
Duty
Cooling Capacity @ 15°C(1)
kW
1 2
Total absorbed power(1 )/(3 )
kW
2 .9 4 5
Cooling Capacity @ 7°C(2)
kW
8
Total absorbed power(2 )/(3 )
kW
3 .1 7 5
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 1 0 A
Compressors
Number of compressors
/
1
Number of circuits
/
1
Total absorbed power(1 )
kW
2 .4 4
Total absorbed current(1 )
A
4 .9 6
Total absorbed power(2 )
kW
2 .6 7
Total absorbed current(2 )
A
5 .3
Fans
Number of fans
/
1
Nominal absorbed power
kW
0 .1 3 5
Nominal absorbed current
A
0 .4 4
Total airflow
m³/h
3 5 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
0 .3 7
Nominal absorbed current
A
1
Water flow rate
m³/h
1 .0 /3 .5
Available head pressure
bar
2 .7 /1 .5
Tank volume
L
1 0
Water
connections
inlet/outlet dimension
(BSP)
inch
1
Dimensions
of unit
Width
mm
7 3 0
Depth
mm
1 1 9 0
Height
mm
8 9 0
Net weight
Kg
2 0 0
Dimensions
of package
Width
mm
8 9 0
Depth
mm
1 3 3 0
Height
mm
1 0 8 5
Gross weight
Kg
2 3 0
Sound pressure level (4 )
dB(A)
6 1
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-15
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-15
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 15
Duty
Cooling Capacity @ 15°C(1)
kW
1 7 .7 5
Total absorbed power(1 )/(3 )
kW
4 .3 2 5
Cooling Capacity @ 7°C(2)
kW
1 2 .8
Total absorbed power(2 )/(3 )
kW
4 .8 2 5
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 1 0 A
Compressors
Number of compressors
/
1
Number of circuits
/
1
Total absorbed power(1 )
kW
3 .4
Total absorbed current(1 )
A
6 .2 8
Total absorbed power(2 )
kW
3 .9
Total absorbed current(2 )
A
7 .0 8
Fans
Number of fans
/
1
Nominal absorbed power
kW
0 .3 7 5
Nominal absorbed current
A
1
Total airflow
m³/h
6 5 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
0 .5 5
Nominal absorbed current
A
2
Water flow rate
m³/h
1 .5 /3 .5
Available head pressure
bar
3 .2 /1 .8
Tank volume
L
1 5
Water
connections
inlet/outlet dimension (BSP)
inch
1
Dimensions
of unit
Width
mm
7 3 0
Depth
mm
1 1 9 0
Height
mm
8 9 0
Net weight
Kg
2 0 5
Dimensions
of package
Width
mm
8 9 0
Depth
mm
1 3 3 0
Height
mm
1 0 8 5
Gross weight
Kg
2 3 5
Sound pressure level (4 )
dB(A)
6 2
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-20
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-20
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 20
Duty
Cooling Capacity @ 15°C(1)
kW
2 1 .3
Total absorbed power(1 )/(3 )
kW
5 .0 2 5
Cooling Capacity @ 7°C(2)
kW
1 5 .3
Total absorbed power(2 )/(3 )
kW
5 .4 2 5
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 1 0 A
Compressors
Number of compressors
/
1
Number of circuits
/
1
Total absorbed power(1 )
kW
4 .1
Total absorbed current(1 )
A
7 .5
Total absorbed power(2 )
kW
4 .5
Total absorbed current(2 )
A
8 .1 1
Fans
Number of fans
/
1
Nominal absorbed power
kW
0 .3 7 5
Nominal absorbed current
A
1
Total airflow
m³/h
6 5 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
0 .5 5
Nominal absorbed current
A
2
Water flow rate
m³/h
1 .5 /3 .5
Available head pressure
bar
3 .2 /1 .8
Tank volume
L
1 5
Water
connections
inlet/outlet dimension (BSP)
inch
1
Dimensions
of unit
Width
mm
7 3 0
Depth
mm
1 1 9 0
Height
mm
8 9 0
Net weight
Kg
2 1 0
Dimensions
of package
Width
mm
8 9 0
Depth
mm
1 3 3 0
Height
mm
1 0 8 5
Gross weight
Kg
2 4 0
Sound pressure level (4 )
dB(A)
6 2
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-30
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-30
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 30
Duty
Cooling Capacity @ 15°C(1)
kW
3 0
Total absorbed power(1 )/(3 )
kW
7 .7 3
Cooling Capacity @ 7°C(2)
kW
2 1 .5
Total absorbed power(2 )/(3 )
kW
8 .5 3
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
1
Number of circuits
/
1
Total absorbed power(1 )
kW
6 .3
Total absorbed current(1 )
A
1 2 .1 7
Total absorbed power(2 )
kW
7 .1
Total absorbed current(2 )
A
1 3 .2
Fans
Number of fans
/
1
Nominal absorbed power
kW
0 .6 8
Nominal absorbed current
A
1 .5
Total airflow
m³/h
9 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
0 .7 5
Nominal absorbed current
A
2
Water flow rate
m³/h
3 /7
Available head pressure
bar
3 .4 /1 .5
Tank volume
L
3 0
Water
connections
inlet/outlet dimension (BSP)
inch
1 ¼
Dimensions
of unit
Width
mm
8 0 0
Depth
mm
1 4 2 0
Height
mm
9 6 0
Net weight
Kg
3 5 5
Dimensions
of package
Width
mm
9 6 0
Depth
mm
1 6 2 0
Height
mm
1 2 0 0
Gross weight
Kg
4 0 0
Sound pressure level (4 )
dB(A)
6 2
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m distance
from the unit at condenser side and at 1.2m from the ground.
HL B-40
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-40
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 40
Duty
Cooling Capacity @ 15°C(1)
kW
3 8 .5
Total absorbed power(1 )/(3 )
kW
8 .6 1
Cooling Capacity @ 7°C(2)
kW
2 5 .5
Total absorbed power(2 )/(3 )
kW
9 .3 7
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
1
Number of circuits
/
1
Total absorbed power(1 )
kW
6 .8
Total absorbed current(1 )
A
1 3 .0
Total absorbed power(2 )
kW
7 .5
Total absorbed current(2 )
A
1 3 .9
Fans
Number of fans
/
1
Nominal absorbed power
kW
1 .1
Nominal absorbed current
A
3 .1
Total airflow
m³/h
1 2 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
0 .7 5
Nominal absorbed current
A
2
Water flow rate
m³/h
4 /7
Available head pressure
bar
3 .4 /1 .5
Tank volume
L
3 0
Water
connections
inlet/outlet dimension (BSP)
inch
1 ¼
Dimensions
of unit
Width
mm
8 0 0
Depth
mm
1 4 2 0
Height
mm
9 6 0
Net weight
Kg
3 6 0
Dimensions
of package
Width
mm
9 6 0
Depth
mm
1 6 2 0
Height
mm
1 2 0 0
Gross weight
Kg
4 0 5
Sound pressure level (4 )
dB(A)
6 5
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-50
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-50
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 50
Duty
Cooling Capacity @ 15°C(1)
kW
4 6 .6
Total absorbed power(1 )/(3 )
kW
9 .8 0
Cooling Capacity @ 7°C(2)
kW
3 0
Total absorbed power(2 )/(3 )
kW
1 0 .7 0
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
1
Number of circuits
/
1
Total absorbed power(1 )
kW
7 .9 5
Total absorbed current(1 )
A
1 5 .3
Total absorbed power(2 )
kW
8 .8 5
Total absorbed current(2 )
A
1 6 .4
Fans
Number of fans
/
1
Nominal absorbed power
kW
1 .1
Nominal absorbed current
A
3 .1
Total airflow
m³/h
1 2 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
0 .7 5
Nominal absorbed current
A
2
Water flow rate
m³/h
5 /7
Available head pressure
bar
3 .4 /1 .5
Tank volume
L
3 0
Water
connections
inlet/outlet dimension (BSP)
inch
1 ¼
Dimensions
of unit
Width
mm
8 0 0
Depth
mm
1 4 2 0
Height
mm
9 6 0
Net weight
Kg
3 7 0
Dimensions
of package
Width
mm
9 6 0
Depth
mm
1 6 2 0
Height
mm
1 2 0 0
Gross weight
Kg
4 1 5
Sound pressure level (4 )
dB(A)
6 5
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-80
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-80
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 80
Duty
Cooling Capacity @ 15°C(1)
kW
7 7 .2
Total absorbed power(1 )/(3 )
kW
1 6 .8 2
Cooling Capacity @ 7°C(2)
kW
5 1 .0
Total absorbed power(2 )/(3 )
kW
1 8 .3 5
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
2
Number of circuits
/
1
Total absorbed power(1 )
kW
1 3 .5
Total absorbed current(1 )
A
2 6 .0
Total absorbed power(2 )
kW
1 5 .0
Total absorbed current(2 )
A
2 7 .9
Fans
Number of fans
/
2
Nominal absorbed power
kW
2 .2
Nominal absorbed current
A
6 .2
Total airflow
m³/h
2 4 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
1 .1
Nominal absorbed current
A
3
Water flow rate
m³/h
6 /1 1
Available head pressure
bar
2 .2 /1 .8
Tank volume
L
1 0 0
Water
connections
inlet/outlet dimension (BSP)
inch
2
Dimensions
of unit
Width
mm
1 0 9 5
Depth
mm
2 0 0 0
Height
mm
2 0 5 0
Net weight
Kg
7 3 0
Dimensions
of package
Width
mm
1 2 3 0
Depth
mm
2 3 0 0
Height
mm
2 2 5 0
Gross weight
Kg
8 0 0
Sound pressure level (4 )
dB(A)
6 7
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-90
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-90
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 90
Duty
Cooling Capacity @ 15°C(1)
kW
8 6 .9
Total absorbed power(1 )/(3 )
kW
1 9 .9 0
Cooling Capacity @ 7°C(2)
kW
6 0
Total absorbed power(2 )/(3 )
kW
2 1 .7 0
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
2
Number of circuits
/
1
Total absorbed power(1 )
kW
1 5 .9
Total absorbed current(1 )
A
3 0 .6
Total absorbed power(2 )
kW
1 7 .7
Total absorbed current(2 )
A
3 2 .8
Fans
Number of fans
/
2
Nominal absorbed power
kW
2 .2
Nominal absorbed current
A
6 .2
Total airflow
m³/h
2 4 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
1 .8
Nominal absorbed current
A
5
Water flow rate
m³/h
1 0 /1 6
Available head pressure
bar
3 .3 /2 .0
Tank volume
L
1 0 0
Water
connections
inlet/outlet dimension (BSP)
inch
2
Dimensions
of unit
Width
mm
1 0 9 5
Depth
mm
2 0 0 0
Height
mm
2 0 5 0
Net weight
Kg
7 5 0
Dimensions
of package
Width
mm
1 2 3 0
Depth
mm
2 3 0 0
Height
mm
2 2 5 0
Gross weight
Kg
8 2 0
Sound pressure level (4 )
dB(A)
6 7
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-140
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-140
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 140
Duty
Cooling Capacity @ 15°C(1)
kW
1 2 8 .5
Total absorbed power(1 )/(3 )
kW
3 0 .6 2
Cooling Capacity @ 7°C(2)
kW
8 4
Total absorbed power(2 )/(3 )
kW
3 3 .9 2
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
4
Number of circuits
/
2
Total absorbed power(1 )
kW
2 4 .9
Total absorbed current(1 )
A
4 9 .2
Total absorbed power(2 )
kW
2 8 .2
Total absorbed current(2 )
A
5 3 .2
Fans
Number of fans
/
4
Nominal absorbed power
kW
2 .7 2
Nominal absorbed current
A
6
Total airflow
m³/h
3 6 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
3
Nominal absorbed current
A
7
Water flow rate
m³/h
1 0 /2 2
Available head pressure
bar
3 .7 /2 .2
Tank volume
L
1 2 0
Water
connections
inlet/outlet dimension (BSP)
inch
2 ½
Dimensions
of unit
Width
mm
1 9 1 0
Depth
mm
2 2 5 0
Height
mm
1 9 5 0
Net weight
Kg
1 3 7 0
Dimensions
of package
Width
mm
2 0 5 5
Depth
mm
2 3 7 0
Height
mm
2 2 0 4
Gross weight
Kg
1 4 9 0
Sound pressure level (4 )
dB(A)
6 8
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-160
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-160
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 160
Duty
Cooling Capacity @ 15°C(1)
kW
1 5 3 .0
Total absorbed power(1 )/(3 )
kW
3 4 .4 3
Cooling Capacity @ 7°C(2)
kW
1 0 2 .0
Total absorbed power(2 )/(3 )
kW
3 7 .4 9
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
4
Number of circuits
/
2
Total absorbed power(1 )
kW
2 7 .0
Total absorbed current(1 )
A
5 2 .0
Total absorbed power(2 )
kW
3 0 .1
Total absorbed current(2 )
A
5 5 .8
Fans
Number of fans
/
4
Nominal absorbed power
kW
4 .4
Nominal absorbed current
A
1 2 .4
Total airflow
m³/h
4 8 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
3
Nominal absorbed current
A
7
Water flow rate
m³/h
1 0 /2 2
Available head pressure
bar
3 .7 /2 .2
Tank volume
L
1 2 0
Water
connections
inlet/outlet dimension (BSP)
inch
2 ½
Dimensions
of unit
Width
mm
1 9 1 0
Depth
mm
2 2 5 0
Height
mm
1 9 5 0
Net weight
Kg
1 4 1 0
Dimensions
of package
Width
mm
2 0 5 5
Depth
mm
2 3 7 0
Height
mm
2 2 0 4
Gross weight
Kg
1 5 3 0
Sound pressure level (4 )
dB(A)
6 8
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-180
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-180
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 180
Duty
Cooling Capacity @ 15°C(1)
kW
1 7 0 .0
Total absorbed power(1 )/(3 )
kW
4 0 .2 0
Cooling Capacity @ 7°C(2)
kW
1 2 0 .0
Total absorbed power(2 )/(3 )
kW
4 3 .8 0
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
4
Number of circuits
/
2
Total absorbed power(1 )
kW
3 1 .8
Total absorbed current(1 )
A
6 1 .2
Total absorbed power(2 )
kW
3 5 .4
Total absorbed current(2 )
A
6 5 .6
Fans
Number of fans
/
4
Nominal absorbed power
kW
4 .4
Nominal absorbed current
A
1 2 .4
Total airflow
m³/h
4 8 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
4
Nominal absorbed current
A
1 0 .3
Water flow rate
m³/h
1 6 /2 6
Available head pressure
bar
3 .3 /2 .0
Tank volume
L
1 2 0
Water
connections
inlet/outlet dimension (BSP)
inch
2 ½
Dimensions
of unit
Width
mm
1 9 1 0
Depth
mm
2 2 5 0
Height
mm
1 9 5 0
Net weight
Kg
1 4 5 0
Dimensions
of package
Width
mm
2 0 5 5
Depth
mm
2 3 7 0
Height
mm
2 2 0 4
Gross weight
Kg
1 5 7 0
Sound pressure level (4 )
dB(A)
6 8
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.
HL B-200
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Read more...
HL B-200
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models
HLB 200
Duty
Cooling Capacity @ 15°C(1)
kW
1 9 1 .3
Total absorbed power(1 )/(3 )
kW
4 7 .8 0
Cooling Capacity @ 7°C(2)
kW
1 3 0
Total absorbed power(2 )/(3 )
kW
5 2 .0 0
Electric Supply
V/Ph/Hz
3 8 0 ~4 1 5 /3 /5 0
Refrigerant
/
R4 0 7 C
Compressors
Number of compressors
/
4
Number of circuits
/
2
Total absorbed power(1 )
kW
3 7 .9
Total absorbed current(1 )
A
6 8 .4
Total absorbed power(2 )
kW
4 2 .1
Total absorbed current(2 )
A
7 4 .4
Fans
Number of fans
/
4
Nominal absorbed power
kW
4 .4
Nominal absorbed current
A
1 0 .4
Total airflow
m³/h
6 0 0 0 0
Pump
(standard 3 bar)
Number of pumps
/
1
Nominal absorbed power
kW
5 .5
Nominal absorbed current
A
1 6
Water flow rate
m³/h
1 5 /6 0
Available head pressure
bar
3 .2 /2 .2
Tank volume
L
2 0 0
Water
connections
inlet/outlet dimension (BSP)
inch
3
Dimensions
of unit
Width
mm
2 0 5 0
Depth
mm
2 8 0 0
Height
mm
1 9 5 0
Net weight
Kg
TBC
Dimensions
of package
Width
mm
2 1 9 5
Depth
mm
2 9 2 0
Height
mm
2 2 0 4
Gross weight
Kg
TBC
Sound pressure level (4 )
dB(A)
6 9
Note:
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C.
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C.
(3) refers to compressor, fans,
and pump absorbed power.
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground.

HL B-10
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 10 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
1 2 |
Total absorbed power(1 )/(3 ) |
kW |
2 .9 4 5 |
|
Cooling Capacity @ 7°C(2) |
kW |
8 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
3 .1 7 5 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 1 0 A |
Compressors |
Number of compressors |
/ |
1 |
Number of circuits |
/ |
1 |
|
Total absorbed power(1 ) |
kW |
2 .4 4 |
|
Total absorbed current(1 ) |
A |
4 .9 6 |
|
Total absorbed power(2 ) |
kW |
2 .6 7 |
|
|
Total absorbed current(2 ) |
A |
5 .3 |
Fans |
Number of fans |
/ |
1 |
Nominal absorbed power |
kW |
0 .1 3 5 |
|
Nominal absorbed current |
A |
0 .4 4 |
|
|
Total airflow |
m³/h |
3 5 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
0 .3 7 |
|
Nominal absorbed current |
A |
1 |
|
Water flow rate |
m³/h |
1 .0 /3 .5 |
|
|
Available head pressure |
bar |
2 .7 /1 .5 |
|
Tank volume |
L |
1 0 |
Water
connections |
inlet/outlet dimension
(BSP) |
inch |
1 |
Dimensions
of unit |
Width |
mm |
7 3 0 |
Depth |
mm |
1 1 9 0 |
|
Height |
mm |
8 9 0 |
|
|
Net weight |
Kg |
2 0 0 |
Dimensions
of package |
Width |
mm |
8 9 0 |
Depth |
mm |
1 3 3 0 |
|
Height |
mm |
1 0 8 5 |
|
|
Gross weight |
Kg |
2 3 0 |
|
Sound pressure level (4 ) |
dB(A) |
6 1 |
Note: |
|
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|
(3) refers to compressor, fans,
and pump absorbed power. |
|
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-15
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 15 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
1 7 .7 5 |
Total absorbed power(1 )/(3 ) |
kW |
4 .3 2 5 |
|
Cooling Capacity @ 7°C(2) |
kW |
1 2 .8 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
4 .8 2 5 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 1 0 A |
Compressors |
Number of compressors |
/ |
1 |
Number of circuits |
/ |
1 |
|
Total absorbed power(1 ) |
kW |
3 .4 |
|
Total absorbed current(1 ) |
A |
6 .2 8 |
|
Total absorbed power(2 ) |
kW |
3 .9 |
|
|
Total absorbed current(2 ) |
A |
7 .0 8 |
Fans |
Number of fans |
/ |
1 |
Nominal absorbed power |
kW |
0 .3 7 5 |
|
Nominal absorbed current |
A |
1 |
|
|
Total airflow |
m³/h |
6 5 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
0 .5 5 |
|
Nominal absorbed current |
A |
2 |
|
Water flow rate |
m³/h |
1 .5 /3 .5 |
|
|
Available head pressure |
bar |
3 .2 /1 .8 |
|
Tank volume |
L |
1 5 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
1 |
Dimensions
of unit |
Width |
mm |
7 3 0 |
Depth |
mm |
1 1 9 0 |
|
Height |
mm |
8 9 0 |
|
|
Net weight |
Kg |
2 0 5 |
Dimensions
of package |
Width |
mm |
8 9 0 |
Depth |
mm |
1 3 3 0 |
|
Height |
mm |
1 0 8 5 |
|
|
Gross weight |
Kg |
2 3 5 |
|
Sound pressure level (4 ) |
dB(A) |
6 2 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-20
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 20 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
2 1 .3 |
Total absorbed power(1 )/(3 ) |
kW |
5 .0 2 5 |
|
Cooling Capacity @ 7°C(2) |
kW |
1 5 .3 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
5 .4 2 5 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 1 0 A |
Compressors |
Number of compressors |
/ |
1 |
Number of circuits |
/ |
1 |
|
Total absorbed power(1 ) |
kW |
4 .1 |
|
Total absorbed current(1 ) |
A |
7 .5 |
|
Total absorbed power(2 ) |
kW |
4 .5 |
|
|
Total absorbed current(2 ) |
A |
8 .1 1 |
Fans |
Number of fans |
/ |
1 |
Nominal absorbed power |
kW |
0 .3 7 5 |
|
Nominal absorbed current |
A |
1 |
|
|
Total airflow |
m³/h |
6 5 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
0 .5 5 |
|
Nominal absorbed current |
A |
2 |
|
Water flow rate |
m³/h |
1 .5 /3 .5 |
|
|
Available head pressure |
bar |
3 .2 /1 .8 |
|
Tank volume |
L |
1 5 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
1 |
Dimensions
of unit |
Width |
mm |
7 3 0 |
Depth |
mm |
1 1 9 0 |
|
Height |
mm |
8 9 0 |
|
|
Net weight |
Kg |
2 1 0 |
Dimensions
of package |
Width |
mm |
8 9 0 |
Depth |
mm |
1 3 3 0 |
|
Height |
mm |
1 0 8 5 |
|
|
Gross weight |
Kg |
2 4 0 |
|
Sound pressure level (4 ) |
dB(A) |
6 2 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-30
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 30 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
3 0 |
Total absorbed power(1 )/(3 ) |
kW |
7 .7 3 |
|
Cooling Capacity @ 7°C(2) |
kW |
2 1 .5 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
8 .5 3 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
1 |
Number of circuits |
/ |
1 |
|
Total absorbed power(1 ) |
kW |
6 .3 |
|
Total absorbed current(1 ) |
A |
1 2 .1 7 |
|
Total absorbed power(2 ) |
kW |
7 .1 |
|
|
Total absorbed current(2 ) |
A |
1 3 .2 |
Fans |
Number of fans |
/ |
1 |
Nominal absorbed power |
kW |
0 .6 8 |
|
Nominal absorbed current |
A |
1 .5 |
|
|
Total airflow |
m³/h |
9 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
0 .7 5 |
|
Nominal absorbed current |
A |
2 |
|
Water flow rate |
m³/h |
3 /7 |
|
|
Available head pressure |
bar |
3 .4 /1 .5 |
|
Tank volume |
L |
3 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
1 ¼ |
Dimensions
of unit |
Width |
mm |
8 0 0 |
Depth |
mm |
1 4 2 0 |
|
Height |
mm |
9 6 0 |
|
|
Net weight |
Kg |
3 5 5 |
Dimensions
of package |
Width |
mm |
9 6 0 |
Depth |
mm |
1 6 2 0 |
|
Height |
mm |
1 2 0 0 |
|
|
Gross weight |
Kg |
4 0 0 |
|
Sound pressure level (4 ) |
dB(A) |
6 2 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m distance
from the unit at condenser side and at 1.2m from the ground. |

HL B-40
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 40 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
3 8 .5 |
Total absorbed power(1 )/(3 ) |
kW |
8 .6 1 |
|
Cooling Capacity @ 7°C(2) |
kW |
2 5 .5 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
9 .3 7 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
1 |
Number of circuits |
/ |
1 |
|
Total absorbed power(1 ) |
kW |
6 .8 |
|
Total absorbed current(1 ) |
A |
1 3 .0 |
|
Total absorbed power(2 ) |
kW |
7 .5 |
|
|
Total absorbed current(2 ) |
A |
1 3 .9 |
Fans |
Number of fans |
/ |
1 |
Nominal absorbed power |
kW |
1 .1 |
|
Nominal absorbed current |
A |
3 .1 |
|
|
Total airflow |
m³/h |
1 2 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
0 .7 5 |
|
Nominal absorbed current |
A |
2 |
|
Water flow rate |
m³/h |
4 /7 |
|
|
Available head pressure |
bar |
3 .4 /1 .5 |
|
Tank volume |
L |
3 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
1 ¼ |
Dimensions
of unit |
Width |
mm |
8 0 0 |
Depth |
mm |
1 4 2 0 |
|
Height |
mm |
9 6 0 |
|
|
Net weight |
Kg |
3 6 0 |
Dimensions
of package |
Width |
mm |
9 6 0 |
Depth |
mm |
1 6 2 0 |
|
Height |
mm |
1 2 0 0 |
|
|
Gross weight |
Kg |
4 0 5 |
|
Sound pressure level (4 ) |
dB(A) |
6 5 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-50
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 50 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
4 6 .6 |
Total absorbed power(1 )/(3 ) |
kW |
9 .8 0 |
|
Cooling Capacity @ 7°C(2) |
kW |
3 0 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
1 0 .7 0 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
1 |
Number of circuits |
/ |
1 |
|
Total absorbed power(1 ) |
kW |
7 .9 5 |
|
Total absorbed current(1 ) |
A |
1 5 .3 |
|
Total absorbed power(2 ) |
kW |
8 .8 5 |
|
|
Total absorbed current(2 ) |
A |
1 6 .4 |
Fans |
Number of fans |
/ |
1 |
Nominal absorbed power |
kW |
1 .1 |
|
Nominal absorbed current |
A |
3 .1 |
|
|
Total airflow |
m³/h |
1 2 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
0 .7 5 |
|
Nominal absorbed current |
A |
2 |
|
Water flow rate |
m³/h |
5 /7 |
|
|
Available head pressure |
bar |
3 .4 /1 .5 |
|
Tank volume |
L |
3 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
1 ¼ |
Dimensions
of unit |
Width |
mm |
8 0 0 |
Depth |
mm |
1 4 2 0 |
|
Height |
mm |
9 6 0 |
|
|
Net weight |
Kg |
3 7 0 |
Dimensions
of package |
Width |
mm |
9 6 0 |
Depth |
mm |
1 6 2 0 |
|
Height |
mm |
1 2 0 0 |
|
|
Gross weight |
Kg |
4 1 5 |
|
Sound pressure level (4 ) |
dB(A) |
6 5 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-80
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 80 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
7 7 .2 |
Total absorbed power(1 )/(3 ) |
kW |
1 6 .8 2 |
|
Cooling Capacity @ 7°C(2) |
kW |
5 1 .0 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
1 8 .3 5 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
2 |
Number of circuits |
/ |
1 |
|
Total absorbed power(1 ) |
kW |
1 3 .5 |
|
Total absorbed current(1 ) |
A |
2 6 .0 |
|
Total absorbed power(2 ) |
kW |
1 5 .0 |
|
|
Total absorbed current(2 ) |
A |
2 7 .9 |
Fans |
Number of fans |
/ |
2 |
Nominal absorbed power |
kW |
2 .2 |
|
Nominal absorbed current |
A |
6 .2 |
|
|
Total airflow |
m³/h |
2 4 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
1 .1 |
|
Nominal absorbed current |
A |
3 |
|
Water flow rate |
m³/h |
6 /1 1 |
|
|
Available head pressure |
bar |
2 .2 /1 .8 |
|
Tank volume |
L |
1 0 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
2 |
Dimensions
of unit |
Width |
mm |
1 0 9 5 |
Depth |
mm |
2 0 0 0 |
|
Height |
mm |
2 0 5 0 |
|
|
Net weight |
Kg |
7 3 0 |
Dimensions
of package |
Width |
mm |
1 2 3 0 |
Depth |
mm |
2 3 0 0 |
|
Height |
mm |
2 2 5 0 |
|
|
Gross weight |
Kg |
8 0 0 |
|
Sound pressure level (4 ) |
dB(A) |
6 7 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-90
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 90 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
8 6 .9 |
Total absorbed power(1 )/(3 ) |
kW |
1 9 .9 0 |
|
Cooling Capacity @ 7°C(2) |
kW |
6 0 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
2 1 .7 0 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
2 |
Number of circuits |
/ |
1 |
|
Total absorbed power(1 ) |
kW |
1 5 .9 |
|
Total absorbed current(1 ) |
A |
3 0 .6 |
|
Total absorbed power(2 ) |
kW |
1 7 .7 |
|
|
Total absorbed current(2 ) |
A |
3 2 .8 |
Fans |
Number of fans |
/ |
2 |
Nominal absorbed power |
kW |
2 .2 |
|
Nominal absorbed current |
A |
6 .2 |
|
|
Total airflow |
m³/h |
2 4 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
1 .8 |
|
Nominal absorbed current |
A |
5 |
|
Water flow rate |
m³/h |
1 0 /1 6 |
|
|
Available head pressure |
bar |
3 .3 /2 .0 |
|
Tank volume |
L |
1 0 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
2 |
Dimensions
of unit |
Width |
mm |
1 0 9 5 |
Depth |
mm |
2 0 0 0 |
|
Height |
mm |
2 0 5 0 |
|
|
Net weight |
Kg |
7 5 0 |
Dimensions
of package |
Width |
mm |
1 2 3 0 |
Depth |
mm |
2 3 0 0 |
|
Height |
mm |
2 2 5 0 |
|
|
Gross weight |
Kg |
8 2 0 |
|
Sound pressure level (4 ) |
dB(A) |
6 7 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-140
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 140 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
1 2 8 .5 |
Total absorbed power(1 )/(3 ) |
kW |
3 0 .6 2 |
|
Cooling Capacity @ 7°C(2) |
kW |
8 4 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
3 3 .9 2 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
4 |
Number of circuits |
/ |
2 |
|
Total absorbed power(1 ) |
kW |
2 4 .9 |
|
Total absorbed current(1 ) |
A |
4 9 .2 |
|
Total absorbed power(2 ) |
kW |
2 8 .2 |
|
|
Total absorbed current(2 ) |
A |
5 3 .2 |
Fans |
Number of fans |
/ |
4 |
Nominal absorbed power |
kW |
2 .7 2 |
|
Nominal absorbed current |
A |
6 |
|
|
Total airflow |
m³/h |
3 6 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
3 |
|
Nominal absorbed current |
A |
7 |
|
Water flow rate |
m³/h |
1 0 /2 2 |
|
|
Available head pressure |
bar |
3 .7 /2 .2 |
|
Tank volume |
L |
1 2 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
2 ½ |
Dimensions
of unit |
Width |
mm |
1 9 1 0 |
Depth |
mm |
2 2 5 0 |
|
Height |
mm |
1 9 5 0 |
|
|
Net weight |
Kg |
1 3 7 0 |
Dimensions
of package |
Width |
mm |
2 0 5 5 |
Depth |
mm |
2 3 7 0 |
|
Height |
mm |
2 2 0 4 |
|
|
Gross weight |
Kg |
1 4 9 0 |
|
Sound pressure level (4 ) |
dB(A) |
6 8 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-160
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 160 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
1 5 3 .0 |
Total absorbed power(1 )/(3 ) |
kW |
3 4 .4 3 |
|
Cooling Capacity @ 7°C(2) |
kW |
1 0 2 .0 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
3 7 .4 9 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
4 |
Number of circuits |
/ |
2 |
|
Total absorbed power(1 ) |
kW |
2 7 .0 |
|
Total absorbed current(1 ) |
A |
5 2 .0 |
|
Total absorbed power(2 ) |
kW |
3 0 .1 |
|
|
Total absorbed current(2 ) |
A |
5 5 .8 |
Fans |
Number of fans |
/ |
4 |
Nominal absorbed power |
kW |
4 .4 |
|
Nominal absorbed current |
A |
1 2 .4 |
|
|
Total airflow |
m³/h |
4 8 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
3 |
|
Nominal absorbed current |
A |
7 |
|
Water flow rate |
m³/h |
1 0 /2 2 |
|
|
Available head pressure |
bar |
3 .7 /2 .2 |
|
Tank volume |
L |
1 2 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
2 ½ |
Dimensions
of unit |
Width |
mm |
1 9 1 0 |
Depth |
mm |
2 2 5 0 |
|
Height |
mm |
1 9 5 0 |
|
|
Net weight |
Kg |
1 4 1 0 |
Dimensions
of package |
Width |
mm |
2 0 5 5 |
Depth |
mm |
2 3 7 0 |
|
Height |
mm |
2 2 0 4 |
|
|
Gross weight |
Kg |
1 5 3 0 |
|
Sound pressure level (4 ) |
dB(A) |
6 8 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-180
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 180 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
1 7 0 .0 |
Total absorbed power(1 )/(3 ) |
kW |
4 0 .2 0 |
|
Cooling Capacity @ 7°C(2) |
kW |
1 2 0 .0 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
4 3 .8 0 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
4 |
Number of circuits |
/ |
2 |
|
Total absorbed power(1 ) |
kW |
3 1 .8 |
|
Total absorbed current(1 ) |
A |
6 1 .2 |
|
Total absorbed power(2 ) |
kW |
3 5 .4 |
|
|
Total absorbed current(2 ) |
A |
6 5 .6 |
Fans |
Number of fans |
/ |
4 |
Nominal absorbed power |
kW |
4 .4 |
|
Nominal absorbed current |
A |
1 2 .4 |
|
|
Total airflow |
m³/h |
4 8 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
4 |
|
Nominal absorbed current |
A |
1 0 .3 |
|
Water flow rate |
m³/h |
1 6 /2 6 |
|
|
Available head pressure |
bar |
3 .3 /2 .0 |
|
Tank volume |
L |
1 2 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
2 ½ |
Dimensions
of unit |
Width |
mm |
1 9 1 0 |
Depth |
mm |
2 2 5 0 |
|
Height |
mm |
1 9 5 0 |
|
|
Net weight |
Kg |
1 4 5 0 |
Dimensions
of package |
Width |
mm |
2 0 5 5 |
Depth |
mm |
2 3 7 0 |
|
Height |
mm |
2 2 0 4 |
|
|
Gross weight |
Kg |
1 5 7 0 |
|
Sound pressure level (4 ) |
dB(A) |
6 8 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |

HL B-200
- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C

- Stainless Steel Plate Heat Exchanger
- Microprocessor Control
- Special Coated Condenser Fins for Longer Life
- Integral Stainless Steel Water Tank
- Adjustable LP Switch
- Centrifugal Stainless Steel Pump
- Heavy Duty Industrial Condenser Fan
- Reliable Compressor
- 100% Non-Ferrous Water Circuit
- Ambient Temperature: From -10°C to 43°C
- Water Temperature: From -5°C to 35°C
Models |
|
|
HLB 200 |
Duty |
Cooling Capacity @ 15°C(1) |
kW |
1 9 1 .3 |
Total absorbed power(1 )/(3 ) |
kW |
4 7 .8 0 |
|
Cooling Capacity @ 7°C(2) |
kW |
1 3 0 |
|
|
Total absorbed power(2 )/(3 ) |
kW |
5 2 .0 0 |
|
Electric Supply |
V/Ph/Hz |
3 8 0 ~4 1 5 /3 /5 0 |
|
Refrigerant |
/ |
R4 0 7 C |
Compressors |
Number of compressors |
/ |
4 |
Number of circuits |
/ |
2 |
|
Total absorbed power(1 ) |
kW |
3 7 .9 |
|
Total absorbed current(1 ) |
A |
6 8 .4 |
|
Total absorbed power(2 ) |
kW |
4 2 .1 |
|
|
Total absorbed current(2 ) |
A |
7 4 .4 |
Fans |
Number of fans |
/ |
4 |
Nominal absorbed power |
kW |
4 .4 |
|
Nominal absorbed current |
A |
1 0 .4 |
|
|
Total airflow |
m³/h |
6 0 0 0 0 |
Pump
(standard 3 bar) |
Number of pumps |
/ |
1 |
Nominal absorbed power |
kW |
5 .5 |
|
Nominal absorbed current |
A |
1 6 |
|
Water flow rate |
m³/h |
1 5 /6 0 |
|
|
Available head pressure |
bar |
3 .2 /2 .2 |
|
Tank volume |
L |
2 0 0 |
Water
connections |
inlet/outlet dimension (BSP) |
inch |
3 |
Dimensions
of unit |
Width |
mm |
2 0 5 0 |
Depth |
mm |
2 8 0 0 |
|
Height |
mm |
1 9 5 0 |
|
|
Net weight |
Kg |
TBC |
Dimensions
of package |
Width |
mm |
2 1 9 5 |
Depth |
mm |
2 9 2 0 |
|
Height |
mm |
2 2 0 4 |
|
|
Gross weight |
Kg |
TBC |
|
Sound pressure level (4 ) |
dB(A) |
6 9 |
Note: |
|||
(1) water outlet temp = 15°C ;
water DELTA T = 5°C; ambient temperature = 25°C. |
|||
(2) water outlet temp = 7°C ;
water DELTA T = 5°C; ambient temperature = 32°C. |
|||
(3) refers to compressor, fans,
and pump absorbed power. |
|||
(4) refers in free field at 10m
distance from the unit at condenser side and at 1.2m from the ground. |